3-Phase Power Phase Loss/Voltage Imbalance — Compressor Overload Trip
Likely causes
Single-phase fuse blown or circuit breaker poor contact
Check: Measure each line-to-line voltage (R-S, S-T, R-T) — if one phase reads 0V, fuse blown or CB open. Measure fuse resistance: normal 0Ω, blown = OL
What to do: Replace blown fuse with same rating (A); if CB poor contact, replace or clean terminal and re-torque (M6: 4~6 N·m)
Line voltage imbalance >5% — causes compressor overcurrent
Check: Measure 3-phase line voltages (e.g. R:210V, S:220V, T:195V): imbalance(%) = max deviation ÷ average × 100. Above 5% = compressor current up to 25% higher
What to do: If imbalance originates at utility supply, report to power company. If internal wiring imbalance, redistribute loads or reinforce wiring
Main power terminal bolts loose/oxidized — increased contact resistance causes voltage drop
Check: Visually inspect terminal block bolts: oxidation (black or blue marks), burn marks, loose bolts. With thermal camera, imbalanced phase terminal runs 15°C or more above other phases
What to do: Sand oxidized terminals and retighten: M6 bolts 4~6 N·m, M8 bolts 8~10 N·m. If severe oxidation, replace terminal block
Magnetic contactor (MC) contact burned — incomplete conduction
Check: Measure MC 3-phase output terminal voltages — normal = same as input; if one phase output is low or 0V, that contact is burned. Direct inspection: look for burn marks or contact welding (stuck closed)
What to do: Replace MC contact kit or entire MC; after replacement, remeasure voltages to confirm 3-phase balance
Phase loss protection relay not installed or set incorrectly
Check: Check if phase protection relay exists in the control panel. If present, verify trip voltage setting — recommended trip at ≤85% of rated voltage
What to do: If not installed, add 3-phase phase loss/reverse/imbalance protection relay. Set trip at ≤85%. Install position: upstream of MC (line side)
Compressor winding ground fault — repeated overload trips due to poor insulation
Check: Measure insulation resistance (megger): compressor terminal-to-ground ≥1MΩ = normal; below 0.1MΩ = confirmed winding ground fault. Also measure 3-phase winding resistance — balanced = normal; unbalanced = open or short circuit
What to do: If insulation resistance <0.1MΩ, compressor replacement is unavoidable. Mandatory system flushing and filter drier replacement before installing new compressor
When 3-phase voltage imbalance exceeds 5%, compressor current can increase by up to 25% — this is why repeated trips occur even with the same MCB rating. Never look at current alone; always measure all three line voltages simultaneously
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting