Excessive Heat Load from Direct Sunlight or Lighting
Likely causes
Direct sunlight exposure — 20~30% capacity reduction
Check: Check direct sunlight exposure times at showcase location — ambient above 27°C + direct sunlight simultaneously causes serious capacity reduction
What to do: Apply UV-blocking film or install blinds; consider relocating showcase; if shading not possible, increase refrigeration capacity
Excessive ceiling lighting heat load — fluorescent/halogen other than LED
Check: Check lighting type directly above showcase — halogen/fluorescent above 200W = serious heat load; verify if replaced with LED
What to do: Replace with LED lighting (4000K, CRI 80+ recommended); adjust lighting direction to minimize direct exposure
Internal showcase LED heat generation
Check: Measure internal LED surface temperature — above 50°C = excessive heat; verify LED driver output (12V/24V normal); check for non-spec LED replacements
What to do: Replace with spec LED and driver; if needed, verify LED heatsink condition
Showcase ambient above 27°C = 20~30% cooling capacity reduction; add direct sunlight and setpoint maintenance becomes impossible — location selection and shading are the fundamental measures
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Temperature Rise Due to Overloading Beyond Load Limit