R-Pro › Field cases › Refrigeration systems
Air Curtain Weakening
Likely causes
Air curtain fan motor running slow or stopped
Check: Measure air curtain outlet airspeed — normal 2.5~3.5 m/s; below 1.5 m/s = fan failure or coil icing
What to do: Replace fan motor; if coil is iced, inspect defrost cycle and manually defrost
Foreign object blocking outlet/inlet
Check: Visually inspect outlet grille — product plastic/paper caught, dust blockage; measure outlet airspeed with anemometer
What to do: Remove foreign objects and clean grille; instruct staff to keep merchandise away from air curtain line
Excessive air curtain load from not using night cover
Check: Check if night cover is used outside business hours — not using increases energy 30~40% and overloads air curtain
What to do: Instruct use of night cover (22:00~07:00 or after business close); replace damaged night cover
High ambient temperature — air curtain penetration reduced
Check: Measure store temperature — above 27°C sharply reduces air curtain efficiency; also check if air conditioning is running
What to do: Adjust store HVAC to 24~25°C; prevent direct ventilation in front of showcase (no direct air conditioner airflow)
Air curtain airspeed below 2.5 m/s cannot maintain temperature against ambient heat — an anemometer is an essential field tool
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting
- Temperature Rise Due to Overloading Beyond Load Limit