Acid Contamination (Post Motor Burnout Circuit Contamination)
Likely causes
Motor burnout causing copper plating throughout circuit
Check: Check for acid contamination using oil acid test kit
What to do: Check for acid contamination using oil acid test kit → Recover all refrigerant (contaminated refrigerant requires special disposal) → Flush entire circuit with flushing refrigerant or nitrogen → Simultaneously replace drier, TXV screen, and suction strainer → Install new compressor and evacuate (≤500 μm Hg) → After recharging, replace drier again within 1 week
Oil and refrigerant acidification corroding pipework
Check: Recover all refrigerant (contaminated refrigerant requires special disposal)
What to do: Recover all refrigerant (contaminated refrigerant requires special disposal) → Flush entire circuit with flushing refrigerant or nitrogen → Simultaneously replace drier, TXV screen, and suction strainer → Install new compressor and evacuate (≤500 μm Hg) → After recharging, replace drier again within 1 week
Motor burnout has spread acidic contaminants throughout the circuit. Replacing only the compressor without cleaning will cause re-burnout. Starting a new compressor in a contaminated circuit will cause rapid re-burnout. Always complete circuit cleaning first.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting