R-Pro › Field cases › Refrigeration systems

Temperature Rise Due to Overloading Beyond Load Limit

Likely causes

Merchandise loaded above the Load Limit Line

Check: Locate load limit line marking inside showcase; measure front/rear row temperature difference — above 2°C = suspected overloading

What to do: Remove excess merchandise and relocate within load limit; staff training to prevent recurrence

Air curtain airflow blocked by merchandise

Check: Check airflow path between outlet and inlet — if merchandise blocks airflow, air curtain collapses; measure inlet airspeed with anemometer (30% reduction vs normal = airflow blocked)

What to do: Move merchandise blocking airflow path; clean foreign matter from inlet grille; distribute loading guidelines to staff

Cold air circulation obstructed — improper shelf placement

Check: Check airflow passage behind shelves — if shelves are against rear wall, cold air circulation is blocked; minimum 5cm rear airflow passage required

What to do: Ensure minimum 5cm gap between shelf and rear wall; readjust shelf positions

Field tip

Front/rear row temperature difference above 2°C = overloading or airflow blockage — thermometer is the first verification tool; immediately correct overloading for food safety

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases