BS Unit Valve Malfunction During Simultaneous Cooling/Heating Operation
Likely causes
BS unit valve coil open circuit or resistance failure — valve switching impossible
Check: Measure BS unit valve coil resistance: normal 20–60Ω → check for open circuit (infinity) or short (0Ω) → check LED indicator (cooling=red, heating=blue)
What to do: Replace faulty coil → confirm LED color switching after replacement → retry simultaneous cooling/heating operation
BS unit PCB control output failure — coil normal but no signal output
Check: After confirming normal coil resistance → measure PCB output pin voltage (normal DC 12–24V signal) → if no signal confirmed, PCB failure diagnosis
What to do: Replace BS unit PCB → re-confirm address settings → verify normal LED display, then test simultaneous cooling/heating operation
BS unit refrigerant pipe valve seat wear — incomplete cooling/heating separation
Check: Measure gas pipe temperature at cooling-mode indoor unit → verify gas pipe low temperature during cooling (normal = low pressure gas during cooling) → check for reverse refrigerant flow symptoms
What to do: Recover refrigerant → replace BS unit valve assembly → nitrogen leak test after reassembly → re-verify simultaneous cooling/heating operation
Check BS unit LED to instantly identify valve status: cooling=red, heating=blue — if LED state doesn't match actual operation mode, suspect coil or PCB failure.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- EEV Stuck — Reduced Cooling/Heating Capacity
- Indoor Unit Drain Pump Malfunction Causing Water Leak
- Indoor Unit Fan Abnormal Noise and Vibration
- Remote Control Reception Failure — Commands Not Transmitted
- Horizontal Indoor Unit Airflow Louver Malfunction
- P/Q Communication Wire Open/Short Circuit — Indoor Unit Communication Error