Circuit breaker keeps tripping
Likely causes
Excessive compressor inrush current (defective start capacitor)
Check: Identify breaker type (overcurrent trip vs. ground fault trip)
What to do: Identify breaker type (overcurrent trip vs. ground fault trip) → Isolate loads individually and test to pinpoint faulty load → Measure compressor winding insulation resistance to ground (≥1MΩ) → Measure inrush current and check capacitor capacity → Verify circuit breaker rated capacity is appropriate
Ground fault (damaged wiring insulation, compressor winding ground)
Check: Isolate loads individually and test to pinpoint faulty load
What to do: Isolate loads individually and test to pinpoint faulty load → Measure compressor winding insulation resistance to ground (≥1MΩ) → Measure inrush current and check capacitor capacity → Verify circuit breaker rated capacity is appropriate
Undersized or aged circuit breaker
Check: Measure compressor winding insulation resistance to ground (≥1MΩ)
What to do: Measure compressor winding insulation resistance to ground (≥1MΩ) → Measure inrush current and check capacitor capacity → Verify circuit breaker rated capacity is appropriate
Overload (refrigerant overcharge, high condensing pressure)
Check: Measure inrush current and check capacitor capacity
What to do: Measure inrush current and check capacitor capacity → Verify circuit breaker rated capacity is appropriate
Insulation resistance measurement is mandatory when an ELCB trips
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting