Cloudy or Opaque Ice

Likely causes

High water TDS (excess dissolved solids)

Check: Measure incoming water TDS with TDS meter — target 50~150 ppm; above 300 ppm = poor water quality

What to do: Install RO filter or replace filter cartridge; adjust to TDS below 150 ppm

Insufficient water circulation (poor spray)

Check: Visually inspect spray nozzles — blocked holes = uneven spray; measure circulation pump flow rate

What to do: Remove nozzles and clean with acid-based descaler; clean pump impeller of scale deposits

Heavy scale on ice-making plate

Check: Check scale thickness on evaporator plate — above 2mm recommend replacement; visually confirm scale particles on ice surface

What to do: Circulate nickel-safe cleaner 1:16 dilution for 1 hour → rinse 3 times; above 2mm replace plate

Freezing too fast (over-cooling)

Check: Log cycle timer — freeze cycle below 10 min = over-cooling suspect; suction pressure below -20°C saturation = overcharge or EEV over-opening

What to do: Readjust EEV superheat to 4~6°C; if refrigerant overcharged, recover and recharge

Field tip

Clear ice requires TDS 50~150 ppm + adequate circulation — check water quality first, refrigeration system second