Ice-Making Cycle Repeated Restart

Likely causes

Thickness sensor contamination

Check: Visually inspect thickness sensor surface for scale/slime deposits; test if it moves freely

What to do: Clean sensor surface with nickel-safe cleaner and recalibrate; replace if plating is worn off

Ice-making timer setting error

Check: Check control board timer parameters — normal freeze 12~18 min, harvest 2~4 min; verify no parameter drift

What to do: Reset to factory defaults and reprogram; replace control board if settings drift repeatedly

Cycle incomplete due to refrigerant shortage

Check: Suction pressure gauge — R-404A @-15°C saturation 0.37 MPa; below this = refrigerant shortage

What to do: Detect and repair leak → vacuum 30 min → recharge to specification

Incomplete harvest (ice release failure)

Check: Check evaporator temperature during harvest — must reach +8°C for ice release; if not, check hot gas path

What to do: Check electrical signal and operation of hot gas bypass valve; measure coil resistance and replace if faulty

Hot gas solenoid valve failure

Check: Measure valve coil resistance — normal 10~30Ω; open or short circuit = replace; no temp rise during harvest = valve not operating

What to do: Replace coil or entire valve; verify harvest temperature reaches +8°C after replacement

Water level sensor error

Check: Measure sensor terminal voltage — open with no water, closed with water = normal; scale buildup causes malfunction

What to do: Clean sensor probe and retest; replace if errors persist — prevent recurrence with RO filter for water quality

Field tip

70% of cycle restart cases are due to thickness sensor contamination or hot gas valve failure — check these two first

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.