R-Pro › Field cases › Heat pumps

Cold Air Complaint During Reverse-Cycle Defrost

Likely causes

During reverse-cycle defrost, 4-way valve switches to cooling mode, causing indoor unit to act as evaporator

Check: Inspect with instruments or visually

What to do: Stop indoor fan immediately at defrost start — check PCB parameter or jumper settings (refer to manufacturer service manual)

No logic (including aux heater interlock) to stop indoor fan during defrost, or the logic is faulty

Check: Inspect with instruments or visually

What to do: Verify aux heater installation and check operation (measure heater resistance, normal: several hundred Ω)

Auxiliary electric heater not installed or malfunctioning

Check: Inspect with instruments or visually

What to do: Set 4-way valve switching delay timer — recommend fan stop first, then 4-way valve switch after 3–5 seconds

Excessively high defrost frequency causing perceived discomfort

Check: Inspect with instruments or visually

What to do: Recheck defrost cycle interval and defrost entry temperature settings (typical: 90–120 min intervals at outdoor -5°C)

4-way valve switching delay

Check: cold air discharged for several seconds at defrost start

What to do: If PCB is suspected faulty, replace defrost control board

Field tip

Fan stop check at defrost start: force defrost mode via remote and verify indoor fan stops within 10 seconds.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases