Discharge Air Temperature Below 40°C During Heating
Likely causes
Refrigerant shortage
Check: low high-side pressure → reduced condensing temperature
What to do: Record high/low pressure and discharge/suction temperature simultaneously → identify refrigerant shortage pattern (low HP, high superheat)
Indoor heat exchanger fouled
Check: reduced air-to-refrigerant heat transfer
What to do: Measure 4-way valve coil voltage (AC220V or DC12V) → if correct voltage but incomplete switching, replace valve
4-way valve incomplete switching
Check: refrigerant partially leaking to cooling circuit
What to do: Measure indoor coil airflow and clean filter → clean coil surface and recheck discharge temperature
Compressor compression efficiency degraded (worn valves)
Check: cannot raise discharge temperature
What to do: Check compressor current vs. frequency graph → if current is low and frequency is at upper limit, reconfigure inverter parameters
Inverter frequency upper limit restricted
Check: insufficient compressor capacity
What to do: If refrigerant shortage confirmed: detect leak and recharge; verify R-410A high pressure normal range of 22–25 bar
To check 4-way valve: in heating mode, touch valve body — if temperature difference between cooling-side and heating-side pipes is less than 10°C, incomplete switching is confirmed
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Ground Loop Antifreeze Concentration Insufficient — Freezing / Poor Heat Transfer
- Heating COP Drop at Low Outdoor Temp (Below -10°C)
- Excessive Frosting on Air-Source Outdoor Unit (Defrost Failure)
- Auxiliary Electric Heater (Backup Heater) Malfunction
- Refrigerant Undercharge/Overcharge — Winter-Specific Symptoms
- Cold Air Complaint During Reverse-Cycle Defrost