R-Pro › Field cases › Heat pumps

Ground Loop Antifreeze Concentration Insufficient — Freezing / Poor Heat Transfer

Likely causes

Only water added during leak makeup — antifreeze concentration diluted

Check: Measure concentration immediately on-site with refractometer — add at least -5°C buffer below minimum ground temperature (ethylene glycol basis)

What to do: Drain part of system and inject concentrate to correct concentration → maintain 30–35% when protection below -10°C needed → find and repair leak, refill with properly mixed antifreeze

Antifreeze degradation over time — pH drop, reduced corrosion inhibition

Check: Measure pH — below 7 or brown color = degraded; visually check color and viscosity; recommend annual or more frequent inspection

What to do: Full replacement if pH below 7 or brown color → flush strainer and heat exchanger simultaneously → regular check of concentration, pH, and color before fall season

High concentration setting (>50%) increases viscosity and reduces flow — actually degrades performance

Check: Measure concentration with refractometer — above 35% check for possible flow reduction; compare flow meter reading to design

What to do: If concentration exceeds target (30–35% for protection below -10°C), dilute by draining part and adding water → re-verify flow → consider installing ground temperature sensor for better freeze prediction

Field tip

Refractometer measurement is possible on-site immediately — checking concentration, pH, and color together before fall season (Sep–Oct) prevents most freeze accidents.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases