Refrigerant Undercharge/Overcharge — Winter-Specific Symptoms
Likely causes
[Undercharge] Leaks accumulated during summer manifest as first symptoms entering winter
Check: excessively low suction pressure
What to do: After heating mode stabilizes (15 min), simultaneously record HP, LP, suction superheat, and discharge superheat → distinguish undercharge vs. overcharge pattern
[Undercharge] Frost zone on suction pipe shrinks + suction superheat increases to over 10°C
Check: Inspect with instruments or visually
What to do: [Undercharge check] R-410A standard: at 0°C outdoor during heating, LP should be ~6.5–7.5 bar; deviation indicates undercharge → detect leak and recharge
[Overcharge] Charged to summer cooling mode standard
Check: risk of liquid refrigerant entering compressor during winter heating
What to do: [Overcharge check] Repeated HP trips over 27 bar + suction superheat 0–2°C → liquid refrigerant risk; recover some refrigerant then remeasure
[Overcharge] High pressure rises excessively (over 27 bar for R-410A)
Check: repeated high-pressure trip
What to do: When adding refrigerant, simultaneously monitor outdoor temp, suction superheat, and liquid line subcooling (target 5–8°C) → add in small increments
Refrigerant added without a reference standard
Check: especially difficult to judge on inverter units due to load fluctuation
What to do: For inverter units, switch to maximum frequency lock mode (service mode) before charging measurement — stable load conditions are essential
Always record outdoor temperature before winter refrigerant charging. R-410A target: during heating at 0°C outdoor — suction superheat 5–8°C AND liquid line subcooling 5–8°C simultaneously indicates correct charge
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Ground Loop Antifreeze Concentration Insufficient — Freezing / Poor Heat Transfer
- Heating COP Drop at Low Outdoor Temp (Below -10°C)
- Discharge Air Temperature Below 40°C During Heating
- Excessive Frosting on Air-Source Outdoor Unit (Defrost Failure)
- Auxiliary Electric Heater (Backup Heater) Malfunction
- Cold Air Complaint During Reverse-Cycle Defrost