Heating COP Drop at Low Outdoor Temp (Below -10°C)

Likely causes

Evaporation pressure drops excessively below -10°C

Check: reduced compressor suction density

What to do: Measure suction/discharge pressure and superheat simultaneously → compare to design specs at low-temperature rating

Suction superheat too high (over 15°C)

Check: insufficient refrigerant circulation

What to do: Check EEV opening log → if superheat control response is delayed at low temp, update firmware or apply manual offset

EEV control logic not adapted for low-temperature operation

Check: Inspect with instruments or visually

What to do: Check refrigerant charge: observe sight glass for bubbles during -10°C operation → replenish if insufficient

Refrigerant charge near lower limit

Check: more sensitive at low temperatures

What to do: Measure outdoor fan current and RPM → inspect fan motor or inverter if deviation exceeds 10% from rated value

Outdoor fan speed control fault

Check: reduced heat recovery from air

What to do: Check low-temp output limit parameter in inverter drive → reset to manufacturer-recommended value

Field tip

If suction pressure drops below 1.5 bar during sub -10°C operation, manually increase EEV opening by 5–10% and check for immediate COP improvement