Compressor Cooling Failure (Insufficient Motor Cooling Gas)

Likely causes

Poor machine room ventilation raising ambient temperature

Check: Measure ambient temperature in machine room (check vs. max rated ambient)

What to do: Measure ambient temperature in machine room (check vs. max rated ambient) → Verify compressor head cooling fan is operating → Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C) → Check for blocked ventilation openings and improve airflow → Check refrigerant charge (suction pressure via low-side gauge)

Compressor head cooling fan failure

Check: Verify compressor head cooling fan is operating

What to do: Verify compressor head cooling fan is operating → Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C) → Check for blocked ventilation openings and improve airflow → Check refrigerant charge (suction pressure via low-side gauge)

Insufficient refrigerant charge reducing motor cooling

Check: Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C)

What to do: Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C) → Check for blocked ventilation openings and improve airflow → Check refrigerant charge (suction pressure via low-side gauge)

Field tip

Suction conditions are normal but external cooling of the compressor is inadequate. Check ambient ventilation and cooling fan. Machine room temperature above 43°C may exceed compressor ratings. Add forced ventilation.