Compressor Cooling Failure (Insufficient Motor Cooling Gas)
Likely causes
Poor machine room ventilation raising ambient temperature
Check: Measure ambient temperature in machine room (check vs. max rated ambient)
What to do: Measure ambient temperature in machine room (check vs. max rated ambient) → Verify compressor head cooling fan is operating → Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C) → Check for blocked ventilation openings and improve airflow → Check refrigerant charge (suction pressure via low-side gauge)
Compressor head cooling fan failure
Check: Verify compressor head cooling fan is operating
What to do: Verify compressor head cooling fan is operating → Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C) → Check for blocked ventilation openings and improve airflow → Check refrigerant charge (suction pressure via low-side gauge)
Insufficient refrigerant charge reducing motor cooling
Check: Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C)
What to do: Use non-contact thermometer on compressor body (normal: ~80°C, danger: ≥100°C) → Check for blocked ventilation openings and improve airflow → Check refrigerant charge (suction pressure via low-side gauge)
Suction conditions are normal but external cooling of the compressor is inadequate. Check ambient ventilation and cooling fan. Machine room temperature above 43°C may exceed compressor ratings. Add forced ventilation.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting