Compressor Discharge Valve Leak Sound

Likely causes

Discharge valve plate worn or broken

Check: Low high-side + high low-side pressure = evidence of valve backflow

What to do: Low high-side + high low-side pressure = evidence of valve backflow → Measure compressor current (may be lower due to reduced load) → Confirm cooling performance degradation → Recover refrigerant and replace compressor → Verify pressure and current normalize after replacement

Valve spring fatigue

Check: Measure compressor current (may be lower due to reduced load)

What to do: Measure compressor current (may be lower due to reduced load) → Confirm cooling performance degradation → Recover refrigerant and replace compressor → Verify pressure and current normalize after replacement

End-of-life from extended operation

Check: Confirm cooling performance degradation

What to do: Confirm cooling performance degradation → Recover refrigerant and replace compressor → Verify pressure and current normalize after replacement

Field tip

High-pressure gas is leaking back through the discharge valve. Cooling efficiency drops. Compressor replacement needed. Never open the compressor without recovering refrigerant first.