Compressor Internal Failure
Likely causes
Motor winding open or inter-turn short
Check: Measure winding resistance (check for open/short)
What to do: Measure winding resistance (check for open/short) → Measure insulation resistance terminal-to-body (≥1MΩ) → Select replacement matching refrigerant, capacity, electrical spec → Recover refrigerant, then replace compressor → Verify oil spec and top up if needed → Evacuate and recharge refrigerant
Internal mechanical wear or seizure
Check: Measure insulation resistance terminal-to-body (≥1MΩ)
What to do: Measure insulation resistance terminal-to-body (≥1MΩ) → Select replacement matching refrigerant, capacity, electrical spec → Recover refrigerant, then replace compressor → Verify oil spec and top up if needed → Evacuate and recharge refrigerant
Internal damage from oil shortage
Check: Select replacement matching refrigerant, capacity, electrical spec
What to do: Select replacement matching refrigerant, capacity, electrical spec → Recover refrigerant, then replace compressor → Verify oil spec and top up if needed → Evacuate and recharge refrigerant
Capacitor and voltage are both normal but the compressor won't start. Internal failure (motor winding or mechanical). Replacement required. Never open the refrigeration cycle without recovering refrigerant. High-pressure release causes serious injury.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting