Compressor Motor Overload (Winding Fault)
Likely causes
Inter-turn winding short causing overcurrent
Check: Measure winding resistance between all terminal pairs (check 3-phase symmetry)
What to do: Measure winding resistance between all terminal pairs (check 3-phase symmetry) → Measure insulation resistance terminal-to-body (≥1MΩ) → Compare operating current to rated → Measure supply voltage balance (≤3% imbalance) → If replacement decided, recover refrigerant and replace
Winding insulation degraded from repeated overheating
Check: Measure insulation resistance terminal-to-body (≥1MΩ)
What to do: Measure insulation resistance terminal-to-body (≥1MΩ) → Compare operating current to rated → Measure supply voltage balance (≤3% imbalance) → If replacement decided, recover refrigerant and replace
Increased internal mechanical friction
Check: Compare operating current to rated
What to do: Compare operating current to rated → Measure supply voltage balance (≤3% imbalance) → If replacement decided, recover refrigerant and replace
Compressor motor overload from winding fault. Measure winding and insulation resistance, then consider replacement. Continued operation with shorted winding causes burnout and carbonized oil contaminating the entire circuit.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting