Compressor Seizure / Lock-up

Likely causes

Seizure from oil shortage

Check: Measure starting current (≥6–8× rated = seizure suspected)

What to do: Measure starting current (≥6–8× rated = seizure suspected) → Check winding and insulation resistance → If high pressure is elevated, recover some refrigerant and retry start → If restart fails, recover all refrigerant → Verify oil quantity and spec, then replace compressor → Evacuate and recharge

Mechanical damage from liquid refrigerant slugging

Check: Check winding and insulation resistance

What to do: Check winding and insulation resistance → If high pressure is elevated, recover some refrigerant and retry start → If restart fails, recover all refrigerant → Verify oil quantity and spec, then replace compressor → Evacuate and recharge

Seized after prolonged shutdown

Check: If high pressure is elevated, recover some refrigerant and retry start

What to do: If high pressure is elevated, recover some refrigerant and retry start → If restart fails, recover all refrigerant → Verify oil quantity and spec, then replace compressor → Evacuate and recharge

Field tip

Power and control signals are normal but the compressor is mechanically seized. Compressor replacement required. Never open the refrigeration circuit without recovering refrigerant.