Compressor thermal trip repeats

Likely causes

Suction pressure too low (refrigerant shortage)

Check: Measure suction and discharge pressures

What to do: Measure suction and discharge pressures → Check refrigerant charge — inspect sight glass for bubbles → Check and clean condenser fins → Clean or replace suction strainer → Check oil level and color → Inspect machine room ventilation

Condensing pressure too high (condenser fouling)

Check: Check refrigerant charge — inspect sight glass for bubbles

What to do: Check refrigerant charge — inspect sight glass for bubbles → Check and clean condenser fins → Clean or replace suction strainer → Check oil level and color → Inspect machine room ventilation

Insufficient or contaminated refrigeration oil

Check: Check and clean condenser fins

What to do: Check and clean condenser fins → Clean or replace suction strainer → Check oil level and color → Inspect machine room ventilation

Suction filter clogged

Check: Clean or replace suction strainer

What to do: Clean or replace suction strainer → Check oil level and color → Inspect machine room ventilation

Ambient temperature excessively high

Check: Check oil level and color

What to do: Check oil level and color → Inspect machine room ventilation

Field tip

Wait at least 10 minutes for cooling before restarting after trip