Defrost Termination Sensor Failure → Premature or Excessive Defrost
Likely causes
Thermistor short circuit → controller senses high temperature → premature defrost termination
Check: Measure sensor terminal resistance: ~6.8kΩ at +10°C, ~10kΩ at 0°C, ~16kΩ at -10°C. 0Ω = short circuit
What to do: Replace with same-spec NTC thermistor 10kΩ@25°C immediately → reinstall and verify operation
Thermistor open circuit → controller sees no temperature → defrost runs to timer maximum
Check: Measure sensor resistance: ∞ (infinite) indicates open circuit. Compare with reference sensor at same temperature
What to do: Replace immediately if open → reconfirm installation position (flush against evaporator outlet fins) → recheck backup timer 25 min
Sensor waterproof sheath damaged → moisture ingress causes irregular resistance fluctuation
Check: Visually inspect sensor sheath (cracks, wear) + verify if resistance fluctuates irregularly regardless of temperature
What to do: Apply self-amalgamating tape for temporary waterproofing → replace with same-spec sensor immediately → use fin clip for secure mounting on reinstall
+10°C termination setpoint applies at the evaporator fins. If sensor is mounted at the drain pan, it reads 5–8°C higher than actual fin temperature, causing premature defrost cutoff.
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting