Defrost Termination Sensor Malfunction
Likely causes
NTC thermistor failure — resistance value drift
Check: Measure NTC thermistor resistance — normal 10kΩ at 25°C; verify resistance changes with temperature; fixed value = failure
What to do: Replace with same spec NTC thermistor; verify defrost termination temperature operation after replacement (+10~+13°C activation)
Thermostat contact failure — defrost not terminating
Check: Check thermostat set temperature — normal defrost termination +10~+13°C; if it doesn't open above this = contact welding or failure
What to do: Replace thermostat (same temperature rating); if contact welded, also inspect heater simultaneously
Sensor position displaced — detached from coil
Check: Check sensor clip mounting position — should be firmly clipped to coil surface; if detached or gapped = temperature sensing delay
What to do: Re-clip sensor to coil; reinforce contact with thermal grease if needed; verify defrost temperature operation after reinstallation
Defrost termination sensor diagnosis order: ①check sensor position → ②measure resistance → ③test thermostat contact — NTC 25°C 10kΩ and thermostat +10~+13°C standards should be memorized