R-Pro › Field cases › Refrigeration systems

Drain Pan Heater Not Working → Drain Line Ice Blockage

Likely causes

Drain pan heater open-circuit → defrost water refreezes before draining, ice accumulates under pan

Check: Measure heater resistance: ~484Ω for 100W, ~242Ω for 200W (at 220V). ∞ = open circuit

What to do: Replace with same-wattage heater → apply power alone and verify surface temperature rises within 10 seconds

Defrost timing error — cooling restarts before drain heater activates, defrost water refreezes immediately

Check: Check sequence diagram: drain heater should pre-activate 5 min before defrost start and remain on ≥10 min after defrost before cooling restarts

What to do: Modify controller sequence settings: drain heater pre-delay +5 min and post-delay +10 min → monitor one full cycle to verify

Drain pipe insufficient slope (<1/50) — pooled water freezes even with heater running

Check: Measure drain pipe slope with level — verify ≥20mm drop per 1m (approximately 2% grade)

What to do: Re-slope drain piping to ≥1/50 (2%) grade + upgrade drain heater to ≥200W for ultra-low temperature environments (≤-35°C)

Field tip

Minimum drain pipe slope is 1/50 (20mm per 1m). In ultra-low temperature cold storage, upgrading drain heater from 100W to 200W alone resolves recurring ice blockage in many cases.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases