R-Pro › Field cases › Refrigeration systems

Electronic Controller (Dixell/Eliwell) Parameter Loss or Probe Error

Likely causes

Power outage caused EEPROM reset — all parameters reverted to factory defaults

Check: Check controller display: if Set Point differs from operating temperature (e.g. 2~5°C), EEPROM reset occurred. Compare product temp vs set temp

What to do: Re-enter parameters (Set/Hy/LSt/USt/dEF etc.) from manufacturer's factory parameter sheet. If unavailable, copy from another unit of same model

NTC probe open/short circuit — displays Er1 (open) or Er2 (short) error

Check: Measure NTC resistance with multimeter: 0°C≈10kΩ, 25°C≈5kΩ. 0Ω = short, OL = open. Verify probe is correctly inserted between evaporator fins

What to do: If open/short, replace with same spec NTC probe. For Dixell: verify NTC 10kΩ B=3977 spec before ordering

NTC connector corrosion/poor contact — moisture infiltration oxidized pins

Check: Disconnect NTC connector at controller rear and visually inspect pins: green/white powder = rust, bent or loose pins. Contact resistance should be <0.5Ω

What to do: Clean with contact cleaner (CRC 2-26 etc.), straighten pins. If severe corrosion, replace entire connector. Apply silicone grease for moisture protection

RTC battery discharged — defrost schedule and clock settings lost

Check: If clock resets to 00:00 after power cycle, RTC battery is discharged. Measure battery voltage: normal 3V, replace if <2.5V

What to do: Replace CR2032 coin cell (every 3~5 years). Parameters are retained after replacement but clock and defrost schedule must be reset

Password lost — cannot access parameter menu

Check: Confirm password prompt on parameter entry. Dixell default: 22 or 0 (varies by model). Eliwell default: 1234. If changed, check with site manager

What to do: Dixell master reset: press UP+DOWN+SET simultaneously for 3 seconds (within 5 seconds of power-on). All parameters reset — re-enter immediately. If reset fails, contact Dixell tech support

Power surges/voltage instability causing repeated controller malfunctions

Check: Measure input voltage: within ±10% of rated (198~242V for 220V). Surge history indicated by bulging capacitor tops or burnt triac marks

What to do: Install surge protection device (SPD). For sites with severe voltage fluctuation, add AVR (automatic voltage regulator). If capacitors aged, replace controller board

Field tip

Saving the parameter sheet (PDF) for that showcase to your smartphone before site visit reduces re-entry time by 90% when an EEPROM reset occurs

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases