Electronic Controller (Dixell/Eliwell) Parameter Loss or Probe Error
Likely causes
Power outage caused EEPROM reset — all parameters reverted to factory defaults
Check: Check controller display: if Set Point differs from operating temperature (e.g. 2~5°C), EEPROM reset occurred. Compare product temp vs set temp
What to do: Re-enter parameters (Set/Hy/LSt/USt/dEF etc.) from manufacturer's factory parameter sheet. If unavailable, copy from another unit of same model
NTC probe open/short circuit — displays Er1 (open) or Er2 (short) error
Check: Measure NTC resistance with multimeter: 0°C≈10kΩ, 25°C≈5kΩ. 0Ω = short, OL = open. Verify probe is correctly inserted between evaporator fins
What to do: If open/short, replace with same spec NTC probe. For Dixell: verify NTC 10kΩ B=3977 spec before ordering
NTC connector corrosion/poor contact — moisture infiltration oxidized pins
Check: Disconnect NTC connector at controller rear and visually inspect pins: green/white powder = rust, bent or loose pins. Contact resistance should be <0.5Ω
What to do: Clean with contact cleaner (CRC 2-26 etc.), straighten pins. If severe corrosion, replace entire connector. Apply silicone grease for moisture protection
RTC battery discharged — defrost schedule and clock settings lost
Check: If clock resets to 00:00 after power cycle, RTC battery is discharged. Measure battery voltage: normal 3V, replace if <2.5V
What to do: Replace CR2032 coin cell (every 3~5 years). Parameters are retained after replacement but clock and defrost schedule must be reset
Password lost — cannot access parameter menu
Check: Confirm password prompt on parameter entry. Dixell default: 22 or 0 (varies by model). Eliwell default: 1234. If changed, check with site manager
What to do: Dixell master reset: press UP+DOWN+SET simultaneously for 3 seconds (within 5 seconds of power-on). All parameters reset — re-enter immediately. If reset fails, contact Dixell tech support
Power surges/voltage instability causing repeated controller malfunctions
Check: Measure input voltage: within ±10% of rated (198~242V for 220V). Surge history indicated by bulging capacitor tops or burnt triac marks
What to do: Install surge protection device (SPD). For sites with severe voltage fluctuation, add AVR (automatic voltage regulator). If capacitors aged, replace controller board
Saving the parameter sheet (PDF) for that showcase to your smartphone before site visit reduces re-entry time by 90% when an EEPROM reset occurs
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting