R-Pro › Field cases › Refrigeration systems

Expansion Device Blockage (TXV / Capillary Tube)

Likely causes

Expansion valve freeze blockage from moisture

Check: Confirm blockage by measuring temperature/pressure across device

What to do: Confirm blockage by measuring temperature/pressure across device → Capillary tube: replace filter drier and backflush with nitrogen → TXV: check sensing bulb attachment and gas charge → Replace filter drier to remove moisture → Evacuate and recharge → Measure subcooling and superheat to verify normal operation

Debris/sludge clogging

Check: Capillary tube: replace filter drier and backflush with nitrogen

What to do: Capillary tube: replace filter drier and backflush with nitrogen → TXV: check sensing bulb attachment and gas charge → Replace filter drier to remove moisture → Evacuate and recharge → Measure subcooling and superheat to verify normal operation

TXV closed due to sensing bulb gas loss

Check: TXV: check sensing bulb attachment and gas charge

What to do: TXV: check sensing bulb attachment and gas charge → Replace filter drier to remove moisture → Evacuate and recharge → Measure subcooling and superheat to verify normal operation

Field tip

Refrigerant pressure is normal but supply to the evaporator is blocked. Inspect expansion device for moisture or debris blockage. Recharging without removing moisture will cause rapid recurrence. Always replace the filter drier.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases