Ground Loop Flow Reduction — Air Entrainment / Cavitation
Likely causes
Air pocket at high point in loop
Check: incomplete purging during fill
What to do: Open automatic/manual air vents at high points — repeat purge until flow meter stabilizes
Expansion tank pressure insufficient or bladder failed
Check: system pressure drops below 0.5 bar
What to do: Check expansion tank nitrogen pre-charge pressure (normally 1.5~2.0 bar); recharge or replace if needed
Circulation pump impeller worn
Check: flow more than 20% below design
What to do: Measure pump current and flow rate — replace impeller or pump if more than 20% below rated
Filter/strainer clogged
Check: Inspect with instruments or visually
What to do: Disassemble and clean strainer — recommend inspection every 6 months
Underground pipe partially crushed or ground settlement
Check: Inspect with instruments or visually
What to do: Pressure-test underground piping at 1.5× operating pressure — check for leaks and crushing
If pump makes hissing or rattling noise on startup, check air vents immediately — air entrainment leads to cavitation and impeller damage.