High Pressure Rise from Refrigerant Overcharge
Likely causes
Excessive refrigerant added during service
Check: Measure subcooling (normal 5–10K; significantly above = overcharge)
What to do: Measure subcooling (normal 5–10K; significantly above = overcharge) → Use recovery equipment to remove some refrigerant and adjust pressure → Determine correct charge by checking subcooling and superheat simultaneously → Record the final charge amount
Refrigerant recharged without weight measurement after parts replacement
Check: Use recovery equipment to remove some refrigerant and adjust pressure
What to do: Use recovery equipment to remove some refrigerant and adjust pressure → Determine correct charge by checking subcooling and superheat simultaneously → Record the final charge amount
Refrigerant overcharge is causing abnormally high pressure. Recover some refrigerant to correct the charge level. Venting refrigerant is prohibited by law. Always use recovery equipment.