Immediate Trip Due to Wiring Short Circuit

Likely causes

Two wires contacting from damaged insulation

Check: Disconnect all loads from wiring

What to do: Disconnect all loads from wiring → Re-close breaker: if trips on wiring alone, wiring is shorted → Reconnect loads one by one to identify which causes the trip → Measure insulation resistance of suspect component and replace → Replace or repair damaged wire insulation

Conductors touching in terminal block

Check: Re-close breaker: if trips on wiring alone, wiring is shorted

What to do: Re-close breaker: if trips on wiring alone, wiring is shorted → Reconnect loads one by one to identify which causes the trip → Measure insulation resistance of suspect component and replace → Replace or repair damaged wire insulation

Internal short circuit in component

Check: Reconnect loads one by one to identify which causes the trip

What to do: Reconnect loads one by one to identify which causes the trip → Measure insulation resistance of suspect component and replace → Replace or repair damaged wire insulation

Field tip

Immediate trip on power-on indicates a short circuit. Disconnect loads one by one to locate the short. Do not force the breaker closed until the short is located. Fire risk.