Low Oil Pressure from Overly Open Pressure Regulating Valve

Likely causes

Oil pressure regulating valve set point drifted

Check: Confirm normal oil pressure range (typically suction pressure + 1.5–3 bar)

What to do: Confirm normal oil pressure range (typically suction pressure + 1.5–3 bar) → Slowly tighten oil pressure regulating valve clockwise to raise pressure → Once target pressure reached, tighten lock nut → If pressure remains unstable after adjustment, consider replacing valve spring

Valve spring aged or broken

Check: Slowly tighten oil pressure regulating valve clockwise to raise pressure

What to do: Slowly tighten oil pressure regulating valve clockwise to raise pressure → Once target pressure reached, tighten lock nut → If pressure remains unstable after adjustment, consider replacing valve spring

Field tip

The oil pressure regulating valve is too open, causing bypass. Re-adjust the valve. Setting oil pressure too high can damage oil seals. Always refer to manufacturer specifications.