Motor Overload Due to Elevated Condensing Pressure
Likely causes
Condenser fan stopped or insufficient airflow
Check: Check condenser fan operation
What to do: Check condenser fan operation → Clean condenser coil → Measure high-side pressure and compare with spec → If non-condensable gas suspected, recover/re-evacuate/recharge
Poor heat rejection from condenser fouling
Check: Clean condenser coil
What to do: Clean condenser coil → Measure high-side pressure and compare with spec → If non-condensable gas suspected, recover/re-evacuate/recharge
Non-condensable gas in circuit
Check: Measure high-side pressure and compare with spec
What to do: Measure high-side pressure and compare with spec → If non-condensable gas suspected, recover/re-evacuate/recharge
Elevated condensing pressure is overloading the compressor motor. Inspect condenser fan and condenser.