No Cooling Due to Refrigerant Leak

Likely causes

Crack or corrosion at flare joints or brazed connections

Check: Use electronic leak detector to locate leak

What to do: Use electronic leak detector to locate leak → Apply soap solution or fluorescent dye to confirm → Recover all refrigerant → Re-braze or re-flare the leak point → Nitrogen pressure test (1.5× design pressure, 30+ min) → Evacuate (≤500 μm Hg) and recharge by weight

Service valve core leak

Check: Apply soap solution or fluorescent dye to confirm

What to do: Apply soap solution or fluorescent dye to confirm → Recover all refrigerant → Re-braze or re-flare the leak point → Nitrogen pressure test (1.5× design pressure, 30+ min) → Evacuate (≤500 μm Hg) and recharge by weight

Compressor shaft seal or discharge valve leak

Check: Recover all refrigerant

What to do: Recover all refrigerant → Re-braze or re-flare the leak point → Nitrogen pressure test (1.5× design pressure, 30+ min) → Evacuate (≤500 μm Hg) and recharge by weight

Field tip

Refrigerant has leaked, causing low cycle pressures. Repair the leak, then recharge. Never vent refrigerant to atmosphere. Illegal and environmentally harmful. Always use recovery equipment.