Oil Contamination (Carbonization or Metal Particles)

Likely causes

Metal particles from internal bearing/piston wear

Check: Take oil sample and check color/viscosity (normal: clear amber)

What to do: Take oil sample and check color/viscosity (normal: clear amber) → Recover all refrigerant and replace compressor → Simultaneously replace filter drier and suction strainer → Flush the circuit (nitrogen flush or flushing refrigerant) → Eliminate root cause (overheating/liquid slugging) before recharging

Oil carbonization from overheating (black discoloration)

Check: Recover all refrigerant and replace compressor

What to do: Recover all refrigerant and replace compressor → Simultaneously replace filter drier and suction strainer → Flush the circuit (nitrogen flush or flushing refrigerant) → Eliminate root cause (overheating/liquid slugging) before recharging

Refrigerant dilution of oil causing lubrication failure

Check: Simultaneously replace filter drier and suction strainer

What to do: Simultaneously replace filter drier and suction strainer → Flush the circuit (nitrogen flush or flushing refrigerant) → Eliminate root cause (overheating/liquid slugging) before recharging

Field tip

Black oil or metal particles indicate internal wear or burnout. Compressor replacement and circuit flushing required. Replacing only the compressor without flushing the circuit will destroy the new compressor quickly. Always flush.