Oil Pump Failure

Likely causes

Oil pump gear or rotor worn

Check: Clean or replace oil filter and strainer

What to do: Clean or replace oil filter and strainer → Measure pressure differential across oil filter → Disassemble and inspect oil pump (gear wear, clearance check) → Replace oil pump using manufacturer-specified parts → Re-measure oil pressure after replacement to confirm normal

Oil filter clogged causing poor oil supply

Check: Measure pressure differential across oil filter

What to do: Measure pressure differential across oil filter → Disassemble and inspect oil pump (gear wear, clearance check) → Replace oil pump using manufacturer-specified parts → Re-measure oil pressure after replacement to confirm normal

Oil strainer fouled

Check: Disassemble and inspect oil pump (gear wear, clearance check)

What to do: Disassemble and inspect oil pump (gear wear, clearance check) → Replace oil pump using manufacturer-specified parts → Re-measure oil pressure after replacement to confirm normal

Field tip

Oil level is normal and valve is correctly set, but oil pressure is low. Inspect the oil pump itself. Oil pump replacement requires compressor disassembly — fully recover refrigerant before proceeding.