R-Pro › Field cases › Refrigeration systems
Partial Case Malfunction in Multi-Case Serial Network — Common Control Line
Likely causes
Bus cable mid-break — all cases beyond break point lose communication
Check: Measure bus cable continuity with multimeter — 0Ω end-to-end = normal; OL = open. Use divide-and-conquer: disconnect mid-point and test each half to locate break
What to do: Replace cable in broken segment. After replacement, sequentially verify communication status of all cases
Duplicate address settings — communication conflict between cases with same address
Check: Check address parameter on each case controller — must be set sequentially from 1 with no duplicates. If two or more cases share the same address, communication conflict occurs
What to do: Reassign duplicate address cases with unique numbers (1, 2, 3…) and restart the entire system
Voltage drop at end cases — insufficient control voltage due to wiring resistance
Check: Compare control voltage at first and last case — if drop exceeds 10% of rated voltage, rewire or upgrade cable
What to do: Upgrade cable cross-section (e.g. 0.75mm² → 1.5mm²); or add booster relay power supply mid-run
Termination resistor (120Ω) missing or incorrectly positioned
Check: Check if 120Ω resistors are installed at both ends of bus. Total bus termination resistance should be 60Ω (two 120Ω in parallel); reading 120Ω = one resistor missing
What to do: Install 120Ω resistors at the two end cases of the bus; if installed in the middle, move to the ends
Solenoid coil noise — interference on communication line
Check: Check if communication errors coincide with solenoid valve open/close timing. Use oscilloscope to check bus line voltage waveform — look for voltage spikes
What to do: Add surge absorption diode or snubber (RC) circuit across solenoid coil; route communication cable separately from power cables
Ground potential difference — potential imbalance between cases causing communication errors
Check: Measure potential difference between each case ground terminal and common ground — normal <1V; above 1V = poor grounding or ground loop
What to do: Consolidate all cases to a single common ground point; measure ground resistance and confirm below 10Ω
First step in multi-case communication diagnostics: disconnect bus cable at the midpoint — test each half separately to narrow down cable break or address conflict to half the network
All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.
Open R-Pro →Related cases
- Aging Room Humidity Control Failure (Unable to Maintain 85~95%RH)
- Ethylene Buildup in Meal Kit/Produce Warehouse — Over-Ripening Due to Ventilation Failure
- End-Zone Temperature Rise (Uneven Cooling)
- Air Curtain Weakening
- Excessive Temperature Rise After Defrost
- Excessive Heat Load from Direct Sunlight or Lighting