R-Pro › Field cases › Refrigeration systems

Partial Frost Due to Expansion Device Abnormality

Likely causes

Expansion valve under-opening (superheat set too high)

Check: TXV: measure superheat and adjust setting (target 5–8K)

What to do: TXV: measure superheat and adjust setting (target 5–8K) → Confirm sensing bulb is tightly strapped and insulated on suction pipe → Capillary tube: replace filter drier and backflush with nitrogen → If moisture is cause, replace drier, re-evacuate, and recharge

Capillary tube partially blocked by debris or moisture

Check: Confirm sensing bulb is tightly strapped and insulated on suction pipe

What to do: Confirm sensing bulb is tightly strapped and insulated on suction pipe → Capillary tube: replace filter drier and backflush with nitrogen → If moisture is cause, replace drier, re-evacuate, and recharge

TXV sensing bulb incorrectly positioned

Check: Capillary tube: replace filter drier and backflush with nitrogen

What to do: Capillary tube: replace filter drier and backflush with nitrogen → If moisture is cause, replace drier, re-evacuate, and recharge

Field tip

Frost concentrated at the evaporator inlet indicates partial blockage or under-opening of the expansion device.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases