Re-frosting Due to Blocked Defrost Drain
Likely causes
Drain outlet blocked by debris or ice
Check: Check drain pan and outlet during defrost (look for ponding)
What to do: Check drain pan and outlet during defrost (look for ponding) → Flush drain with warm water and remove debris → Check drain heater continuity if equipped → Verify drain pipe slope and check for blockage → Run defrost cycle to confirm normal drainage
Drain pipe frozen from drain heater failure
Check: Flush drain with warm water and remove debris
What to do: Flush drain with warm water and remove debris → Check drain heater continuity if equipped → Verify drain pipe slope and check for blockage → Run defrost cycle to confirm normal drainage
Improper drain slope or blocked drain pipe
Check: Check drain heater continuity if equipped
What to do: Check drain heater continuity if equipped → Verify drain pipe slope and check for blockage → Run defrost cycle to confirm normal drainage
Defrost is working but meltwater is not draining, causing repeated re-frosting. Clean the drain.