R-Pro › Field cases › Refrigeration systems

Reduced Cooling Capacity Due to Low Refrigerant Charge

Likely causes

Slow leak from somewhere in the circuit

Check: Check all pipes and joints with leak detector

What to do: Check all pipes and joints with leak detector → Repair any leak first — do not add refrigerant without fixing the leak → Recharge by accurate weight measurement → After charging, measure pressures, superheat, and subcooling → Record the charge amount

Inadequate initial charge

Check: Repair any leak first — do not add refrigerant without fixing the leak

What to do: Repair any leak first — do not add refrigerant without fixing the leak → Recharge by accurate weight measurement → After charging, measure pressures, superheat, and subcooling → Record the charge amount

Minor service port core leak

Check: Recharge by accurate weight measurement

What to do: Recharge by accurate weight measurement → After charging, measure pressures, superheat, and subcooling → Record the charge amount

Field tip

Refrigerant charge is low. Always check for leaks before adding refrigerant. Adding refrigerant without fixing the leak is a temporary measure and causes environmental harm and legal liability.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases