Refrigerant Overcharge or TXV Over-opening

Likely causes

Refrigerant overcharge (subcooling >10°C)

Check: Measure subcooling: condenser outlet temp − condensing sat. temp (normal 5–8°C, overcharge >10°C)

What to do: Measure subcooling: condenser outlet temp − condensing sat. temp (normal 5–8°C, overcharge >10°C) → If subcooling is normal, the issue is TXV superheat setting → Adjust TXV screw clockwise in 1/4-turn steps (raises superheat) → If overcharged, recover excess refrigerant

TXV adjustment spring under-tension (superheat set too low)

Check: If subcooling is normal, the issue is TXV superheat setting

What to do: If subcooling is normal, the issue is TXV superheat setting → Adjust TXV screw clockwise in 1/4-turn steps (raises superheat) → If overcharged, recover excess refrigerant

Field tip

High suction pressure and frost on suction line indicate overcharge or TXV over-opening. Measure subcooling and superheat. Superheat below 3°C risks liquid slugging. Do not set below 5°C.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.