Refrigerant shortage (low suction pressure)
Likely causes
Leak (flare joints, valve packing, weld points)
Check: Measure low-side pressure — confirm normal range for refrigerant type
What to do: Measure low-side pressure — confirm normal range for refrigerant type → Inspect all piping for leaks (electronic detector or soapy water) → Repair leak (re-flare or weld) → Evacuate system and recharge to specified amount → After charging, confirm bubbles disappear from sight glass
Natural reduction from long-term lack of inspection
Check: Inspect all piping for leaks (electronic detector or soapy water)
What to do: Inspect all piping for leaks (electronic detector or soapy water) → Repair leak (re-flare or weld) → Evacuate system and recharge to specified amount → After charging, confirm bubbles disappear from sight glass
Insufficient charge after service work
Check: Repair leak (re-flare or weld)
What to do: Repair leak (re-flare or weld) → Evacuate system and recharge to specified amount → After charging, confirm bubbles disappear from sight glass
Never add refrigerant without first repairing the leak