Start Capacitor Failure Causing Startup Overcurrent
Likely causes
Capacitor capacity degraded or shorted
Check: Measure capacitance (within ±10% of rated)
What to do: Measure capacitance (within ±10% of rated) → Inspect for bulging or leakage → Replace with same specification if faulty → Measure starting current after replacement
Poor capacitor connection
Check: Inspect for bulging or leakage
What to do: Inspect for bulging or leakage → Replace with same specification if faulty → Measure starting current after replacement
Field tip
Inspect and replace the start capacitor if faulty. Always confirm capacitor is discharged before replacement.