Start Capacitor Failure

Likely causes

Capacity degraded from aging

Check: Inspect for bulging, cracking, or leakage

What to do: Inspect for bulging, cracking, or leakage → Measure capacitance (within ±10% of rated) → Prepare replacement of same spec (μF and voltage) → Photograph terminal wiring before disconnecting → Measure starting current after replacement

Damaged by overvoltage or overheating

Check: Measure capacitance (within ±10% of rated)

What to do: Measure capacitance (within ±10% of rated) → Prepare replacement of same spec (μF and voltage) → Photograph terminal wiring before disconnecting → Measure starting current after replacement

Terminal corrosion or poor contact

Check: Prepare replacement of same spec (μF and voltage)

What to do: Prepare replacement of same spec (μF and voltage) → Photograph terminal wiring before disconnecting → Measure starting current after replacement

Field tip

Replace the start capacitor with one of the same specification (μF and voltage rating). Wait 10 minutes after power-off or use a discharge resistor before handling a charged capacitor.