R-Pro › Field cases › Refrigeration systems

Thermal Overload Protector Tripped

Likely causes

Excessive current (refrigerant overcharge, high condensing pressure)

Check: Measure compressor surface temperature (overheating if ≥90°C)

What to do: Measure compressor surface temperature (overheating if ≥90°C) → Measure supply voltage (within ±10% of rated) → Compare operating current with rated current → Check condenser fan and cleanliness → Wait 15–30 minutes for cooling and auto-reset → After reset, eliminate root cause

Compressor overheating from poor ventilation

Check: Measure supply voltage (within ±10% of rated)

What to do: Measure supply voltage (within ±10% of rated) → Compare operating current with rated current → Check condenser fan and cleanliness → Wait 15–30 minutes for cooling and auto-reset → After reset, eliminate root cause

Voltage imbalance or undervoltage

Check: Compare operating current with rated current

What to do: Compare operating current with rated current → Check condenser fan and cleanliness → Wait 15–30 minutes for cooling and auto-reset → After reset, eliminate root cause

Field tip

The thermal overload protector has tripped. Allow cooling and auto-reset, then identify and eliminate the root cause. Do not disable or bypass the overload protector. Risk of compressor burnout and fire.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases