TXV Internal Defect (Diaphragm or Spring Fault)

Likely causes

Diaphragm gas leak causing loss of valve control

Check: Recover all refrigerant

What to do: Recover all refrigerant → Replace TXV with same refrigerant, capacity, and orifice size → Replace filter drier at the same time → Re-install sensing bulb (4–8 o'clock position, insulated) → Evacuate, recharge, run 20 minutes, then measure superheat

Spring aging prevents maintaining set point

Check: Replace TXV with same refrigerant, capacity, and orifice size

What to do: Replace TXV with same refrigerant, capacity, and orifice size → Replace filter drier at the same time → Re-install sensing bulb (4–8 o'clock position, insulated) → Evacuate, recharge, run 20 minutes, then measure superheat

Partial debris blockage of internal orifice

Check: Replace filter drier at the same time

What to do: Replace filter drier at the same time → Re-install sensing bulb (4–8 o'clock position, insulated) → Evacuate, recharge, run 20 minutes, then measure superheat

Field tip

If hunting persists with normal bulb contact and load conditions, the TXV has an internal defect. Replace the TXV. Always use a TXV matched to the refrigerant type and system capacity. Using an R404A TXV in an R22 circuit causes loss of control.

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.