VRF Y-Joint Installation — Horizontal / Inclination Rules

Likely causes

Y-joint orientation + inclination rules

Check: Install Y-joint within ±15° of horizontal (per manufacturer mark). Never install vertically (oil trapping, uneven distribution). Provide 3 m straight pipe after branch (flow stabilization). First 90° bend = ≥0.5 m from branch. Use only certified insulated branch kits.

What to do: Install Y-joint within ±15° of horizontal, following manufacturer orientation mark. Maintain 3 m straight pipe after branch before first 90° bend. Use only manufacturer-certified branch kits (with insulation). Test = run all indoor units simultaneously and verify discharge temperature consistency (±2°C).

Field tip

Y-joint defects = VRF distribution imbalance → some indoor units underperform. Test = run all indoor units simultaneously and verify consistent discharge temperatures. Counterfeit kits lack flammability safety certification for R-32/R-454B = leak risk.