R-ProField casesIce machines

Water Basin/Circulation Pump Slime Contamination

Likely causes

Slime film formed from long-term cleaning neglect

Check: Rub basin interior wall with finger to check stickiness — sticky = slime film formed; also check for odor

What to do: Circulate nickel-safe cleaner 1:16~1:32 for 1 hour → rinse 3 times; schedule preventive cleaning every 3 months

Poor water quality — creating microbial growth environment

Check: TDS measurement — above 300 ppm accelerates microbial growth; also check pH range 6.5~7.5

What to do: Install RO filter or replace cartridge; consider adding silver-ion antibacterial filter to piping

Circulation pump impeller slime coating — flow reduction

Check: Measure basin circulation flow or pump current — slime-coated impeller causes reduced flow and increased current

What to do: Disassemble and clean impeller with acid cleaner; if cause is irregular maintenance, schedule cleaning every 3 months

Field tip

Always use nickel-safe cleaner for slime removal — regular bleach (chlorine) corrodes metal; 1:16 ratio, 1 hour circulation + 3 rinses is the standard

All 565 cases work offline in R-Pro, with error codes for 62 brands and P-T data for 108 refrigerants.

Open R-Pro →

Related cases